DF-52338 — Page 1 of 6
GENERAL
The Fire•Lite FIRE•COMMAND•25/50X is a state-of-the-
art Emergency Voice Evacuation Control Panel (VECP),
with significant technological enhancements that set it apart
from other voice panels. These enhancements include
full supervision in both active (alarm or music) and standby
conditions, optional remote microphone, message and tone
generator backups, independent power feed to each am-
plifier, and full output power per amplifier (including when
using 70 VRMS option) generated while in low battery
condition.
The FIRE•COMMAND•25/50X is suitable (but not limited
to) as an adjunct to most UL listed Fire Alarm Control
Panels (FACP) in applications such as restaurants, schools,
auditoriums, dormitories, theaters, places of worship, mo-
tels, hotels, office buildings, and factories to name a few.
A host of field-programming options, including dual-mes-
sage capability (fire, adverse weather, non-fire, multi-lan-
guage), makes the FIRE•COMMAND•25/50X a very ver-
satile voice evacuation system.
STANDARD FEATURES
• Built-In Power Supply - An internal power supply and
battery charger is built-in to unit.
√ Ground fault detection with diagnostic LED (yellow).
√ Brownout detection with battery transfer.
√ Battery trouble detect with diagnostic LED (yellow).
√ Battery saver operation.
√ Independent AC loss relay provides AC loss delay
per UL, for independent monitoring by DACT (2 Amps at
24 VDC).
√ AC power on LED (green).
√ 18 AH battery charging capacity — up to 7 AH may be
utilized in FIRE•COMMAND enclosure. 12 AH - 18 AH
require Fire•Lite BB-17F battery box.
√ Large, teeter-plate terminal blocks easily accept up to
12 AWG for power terminations.
• Full supervision in both active (alarm or music) or standby
conditions:
√ Amplifier outputs
√ Field wiring (shorts and opens)
√ Message generator
√ All tone generators
√ Microphone
• Integral 25 Watt, 25 VRMS audio amplifier with single
Class A/Class B speaker circuit (expandable to two with
optional 25 watt expander amplifier).
• Integral digital message repeater with 'primary' and
'secondary' dual 30-second message capability or one
60-second customer message.
• Integral supervised microphone.
• Dual Command Input (trigger) circuits field selectable to
be activated from 12 or 24 VDC Notification Appliance
Circuit (reverse polarity) or contact closure.
• Built-in tone generators (field selectable).
• Field-selectable lead-in/trailing tone selection.
• 12 integral diagnostic LED's.
• Optional 70.7 VRMS conversion module available for
each amplifier.
• Optional local playback speaker.
• Optional Remote Microphone Module FC-RM (use
included interface module FC-MIM).
• Optional Distributed Audion Panel (FC-25/50DA).
This document is not intended to be used for installation purposes. We try to keep our product information
up-to-date and accurate. We cannot cover all specific applications or anticipate all requirements. All
specifications are subject to change without notice. For more information, contact:
Fire•Lite Alarms, One Fire-Lite Place, Northford, Connecticut 06472.
Phone: (800) 627-3473 Toll Free FAX: (877) 699-4105 FAX Back:(888) 388-3299
FIRE•COMMAND•25/50X
Emergency Voice Evacuation Control
June 10, 2002
DF-52338 C-025
Section: Emergency Voice Evacuation
www.firelite.com
S2424
Patent # 5,883,573
California
State Fire
Marshal
6911-0075:181
MEA
Commentaires sur ces manuels